Solution · Diesel generators
Generator Monitoring System — DG Performance, Condition & Fuel
Tech OVN's generator monitoring system puts a Titan energy meter on the DG output. It keeps DG energy in separate registers, records DG run hours, load and power factor, and reads the genset controller over RS485 for oil pressure, coolant temperature, battery voltage, alarms and fuel level — so you can track kWh per litre and catch problems before a failure.

At a glance
- Performance
- DG kWh / kVAh in separate registers, DG run hours, load %, PF, voltage, frequency, harmonics, cost per unit.
- Condition
- Read from the genset controller over RS485: oil pressure, coolant temperature, battery voltage, speed, alarms, shutdowns.
- Fuel
- Fuel level from the controller's own fuel sensor — giving kWh per litre and fuel per run.
- Connectivity
- Titan: WiFi / Ethernet (MQTT, Modbus TCP, BACnet/IP). Titan 4G: 4G, MQTT only.
Most Generators Run on a Logbook
A diesel generator is often the most expensive source of power on a site, yet what most owners know about it is an hour-meter reading and a fuel register filled in by hand. Neither says how much electricity the diesel produced, whether the set was loaded sensibly, or that the oil pressure has been sagging for a month.
Generator monitoring replaces the logbook with measurement: energy out, fuel in, engine condition — recorded continuously and visible from anywhere.
Performance — From the Titan Meter
Titan is a dual-source energy meter: grid and generator energy land in separate registers.
DG Energy, Kept Separate
A 12 V DG-on signal switches Titan into its own DG register set — kWh, kvarh and kVAh, per phase and total — so generator energy is never mixed with grid energy.
Run Hours That Match the Energy
Titan records DG run hours itself. Hours alone say the engine was on; hours next to kWh say whether it did useful work.
Load, PF, Voltage & Frequency
Load as a share of the set's rating, per-phase power factor and unbalance, voltage and frequency stability, and harmonics to the 31st — the electrical side of how well the set is running.
Cost per Unit — Grid vs DG
With the diesel price and fuel data, every DG unit gets a real cost, next to the grid tariff — the number that decides how long the set should run.
Condition — From the Genset Controller
The controller already knows how the engine is doing. Titan reads it over RS485 and sends it out with the electrical data.
Engine Readings From the Controller
Titan's RS485 port acts as a Modbus master and polls the genset controller for what it exposes — typically oil pressure, coolant temperature, battery voltage and engine speed.
Alarms, Shutdowns & Failed Starts
Controller alarm and shutdown states, start attempts and maintenance counters are logged with a time stamp, alongside what the electrical side was doing at that moment.
Fuel Level
Fuel level is read from the controller's own fuel sensor — no separate tank sensor to fit when the controller already has one.
One Link for Everything
Electrical and engine data leave the site together — over WiFi or Ethernet with Titan, or over 4G with Titan 4G — to the Energy Intelligence Platform or your own MQTT broker.
Compatibility depends on the controller and the registers it exposes over Modbus RTU — send us the model and we confirm before you order. While RS485 is reading the controller it cannot also serve a BMS on RS485; use Ethernet or MQTT for the BMS.
How to Measure Generator Performance
Six steps, whether you use our hardware or not. Try the numbers for your own set in the DG fuel consumption calculator.
1 · Measure what the set delivers
Meter the DG output in its own registers (kWh, kVAh, load %, PF). An hour meter and a logbook only tell you the engine was running.
2 · Measure what it consumes
Record fuel used over the same period — from the controller's fuel sensor, or from fill records if the controller has none.
3 · Track kWh per litre
Divide kWh by litres. Tracked week on week at similar loads, a falling figure is the earliest sign of an engine, injection or loading problem.
4 · Check the loading
Compare average load with the set's rating. Long runs at light load waste fuel and are a known cause of wet stacking — follow the manufacturer's guidance on minimum load.
5 · Watch electrical quality
Voltage and frequency stability, power factor and phase unbalance show whether the set — and the load on it — is behaving.
6 · Tie it to engine condition
Oil pressure, coolant temperature, battery voltage and alarms from the controller explain why performance moved, and flag service before a failure.
Where It's Used
Any site where a generator matters — for cost, for uptime, or both.
Factories & Plants
DG cost per unit and loading across shifts, compared with the grid tariff.
Hospitals & Data Centres
Standby sets that must start every time: start attempts, battery voltage, alarms and test-run records.
Commercial Buildings & Malls
DG energy split per tenant or floor with Titan Group, for DG backup recovery.
Telecom & Remote Sites
Sets far from anyone, reporting over 4G with no site network.
Rental & AMC Fleets
Every set in the fleet — hours, energy, fuel and alarms — in one view.
Residential Societies
DG backup hours and energy recorded, so maintenance and backup charges are based on measurement.
Which Titan for Your Generator
Every Titan keeps DG energy and run hours. Pick by the network on site and whether you want engine data.
| Titan | Titan 4G | Titan Group | Titan RS485 | |
|---|---|---|---|---|
| Price (+ GST, per meter) | ₹11,000 | ₹11,500 | ₹6,500 / ₹11,000 / ₹11,500 | ₹6,500 |
| DG kWh registers + DG run hours | Yes | Yes | Yes — per circuit (4) | Yes |
| Reads the genset controller (RS485 master) | Yes | Yes | Yes, on WiFi / 4G models | No — RS485 is its only port |
| Data out | WiFi / Ethernet: MQTT, Modbus TCP, BACnet/IP | 4G: MQTT only | Per model | RS485 to a BMS / PLC |
| Best for | Sites with a network | Sites with no network | DG split per tenant / floor | Panel builds wired to a BMS |
See Titan, Titan 4G and Titan Group. CTs are extra, from ₹950 + GST each.
Generator Service in Delhi NCR — OVN Engineers
Tech OVN makes the meter and the platform. For the generator itself, our parent company OVN Engineers sells, rents and services diesel generators and builds AMF panels across Delhi NCR.
Frequently Asked Questions
Generator performance, condition monitoring, fuel and connectivity.
Related
DG fuel consumption calculator
kWh per litre, litres per hour, load % and cost per unit for your set.
Learn More →Diesel genset vs grid
What a DG unit really costs compared with your grid tariff.
Learn More →Titan 4G
4G energy meter with MQTT, for generator sites with no network.
Learn More →What is a dual-source energy meter?
How grid and DG energy are recorded separately.
Learn More →Monitor your generators
Tell us the number of sets, their kVA ratings, the controller model and whether the sites have a network.