DG Fuel Consumption & Efficiency Calculator
Enter your DG set's rating, load, hours and the diesel it actually used. Get litres per hour, kWh per litre, load % and fuel cost per unit — for a 125, 250, 500 kVA or any size set.
Quick Answer
DG efficiency on site = kWh generated ÷ litres of diesel used. Fuel per hour = litres ÷ hours run. Load % = average kW ÷ (kVA × 0.8).
- Fuel per hour depends on load. Fuel per unit (L/kWh) is what tells you whether the set is running well.
- Use real numbers: litres from your fuel register, kWh from a meter on the DG output.
- Track kWh per litre over weeks. A drop at the same load is the early warning.
The figures in the calculator are example inputs only — replace them with your own.
Inputs
Result
How the calculation works
Load % = Average load kW ÷ Rated kW × 100
kWh generated = Average load kW × Hours run
Litres per hour = Litres used ÷ Hours run
kWh per litre = kWh generated ÷ Litres used
Fuel cost per kWh = (Litres used × ₹/L) ÷ kWh generated
The weak link in most DG calculations is the load figure. An “estimated 60% load” can easily be 40% or 80% in reality, and every result above moves with it. Measure the average kW on the DG output with an energy meter for the same period as your fuel reading, and the numbers become reliable.
For an hour-by-hour figure, read the fuel consumption table in your engine maker's datasheet — it gives litres per hour at set load points — and use this calculator to compare it with what your set actually does.
Why kWh per litre is the number to watch
- It separates load from performance. Litres per hour rises and falls with load; kWh per litre at a similar load should stay steady.
- It shows light running. The same set usually gives fewer units per litre at light load than near its rating.
- It exposes fuel losses. If litres go up but kWh does not, the diesel is going somewhere other than the engine — a leak, a wrong register entry or theft.
- It gives a true cost per unit. Compare it with your grid tariff in the diesel genset vs grid calculator.
Measure it automatically instead of by hand
A Titan energy meter on the DG supply takes a 12 V signal when the DG is on and records DG energy (kWh, kvarh, kVAh) in its own registers, separate from grid energy, together with DG run hours, load and power factor. That gives you the kWh and hours side of this calculation continuously, with no manual readings.
For the fuel side, Titan can read the genset controller over its RS485 port, including the level from the controller's fuel sensor, along with the engine readings and alarms the controller reports. Put together, that is units per litre, load and engine condition on one dashboard. See generator monitoring for how the system fits together.
Many DG rooms have no WiFi. For those sites, Titan 4G sends the same data over a mobile network using MQTT.
Frequently asked questions
DG fuel consumption, efficiency and load.
Related products & tools
From a one-off calculation to continuous DG monitoring.
Generator Monitoring System
DG performance and condition monitoring: energy, run hours, load, fuel and engine alarms in one view.
Learn More →Titan — Smart Energy Meter
Class 0.5S 3-phase meter with separate grid and DG registers and DG run hours.
Learn More →Titan 4G
The same meter with a built-in 4G module, for DG rooms and remote sites. MQTT.
Learn More →Diesel Genset vs Grid Calculator
Compare your DG's cost per kWh with your grid tariff.
Learn More →kVA to kW Converter
Convert a DG's kVA rating to kW at any power factor.
Learn More →Track your DG's units per litre automatically
Tell us the DG rating and how many sets. An engineer replies within 24 hours with the meter, CTs and a price.