How to measure it in practice
The manual method
The manual method requires an energy meter on the DG output with a separate DG register (so grid energy and DG energy are not mixed — see our post on dual source energy meters), a fuel delivery log, periodic tank dip readings, and a run-hours record. At the end of each billing period or operational week, you read the DG kWh and cross-reference with fuel used.
This works, but it is slow, prone to recording errors, and gives you no visibility during a run. You can calculate kWh per litre after the fact; you cannot see the load dipping below an acceptable level while it is happening.
The continuous method with Titan
Titan's DG monitoring capability works as follows: a 12 V signal from the genset panel (the DG-on signal) switches Titan into a separate DG register set, recording kWh, kVArh, and kVAh for the DG source independently of grid consumption. Run hours are logged automatically for each DG start. This means every DG run produces a clean, timestamped energy record without manual intervention.
For engine condition, Titan's RS485 port can be configured as a Modbus master to read the genset controller — bringing oil pressure, coolant temperature, battery voltage, engine speed, active alarms, and fuel level (from the controller's own fuel sensor) into the same dataset as the electrical measurements. While RS485 is acting as a Modbus master, it cannot simultaneously serve as a BMS slave — this is an important constraint to plan around in multi-protocol buildings.
For connectivity, the standard Titan (₹11,000 + GST) sends data via WiFi or Ethernet using MQTT, Modbus TCP, or BACnet/IP. For remote sites with no network — DG yards, pump houses, telecom shelters — the Titan 4G (₹11,500 + GST) has a built-in cellular module and sends data via MQTT over its own SIM. RS485 is kept on both models for the genset controller connection. Use the diesel genset vs grid cost tool to model the economics once you have the energy data in hand.
The result is a continuous, correlated record — kWh per litre, load as % of rating, power factor, voltage, frequency, oil pressure, coolant temperature, and alarms — available remotely, for every DG run, without manual data collection.