Compliance Resource
Fire Pump Weekly Test Log Template — NFPA 25 & IS 15301
Reviewed by Ramniwas Gautam, Validation Head, Tech OVN
A free fire-pump test log template, structured to satisfy NFPA 25, IS 15301, NBC 2016 Part 4, and the fire-NOC inspection requirements used by most Indian state authorities. Use it as your weekly logbook, monthly checklist, or hand-off document for a fire-protection contractor.
The on-page version below shows the structure, the required fields, and the testing-frequency table. The formatted PDF is A4-printable, laid out for fire-NOC inspections and insurance surveys.
Testing Frequency at a Glance
The minimum testing schedule a fire-NOC inspector or insurance surveyor will check against. Document every entry against this table. Frequencies are from NFPA 25 (2023 edition); confirm which edition your fire authority or insurer applies.
| Test | Pumps | Frequency | Minimum Duration | Standard |
|---|---|---|---|---|
| No-flow (churn) test | Diesel fire pumps | Weekly | Minimum 30 minutes | NFPA 25 (2023) §8.3.1 |
| No-flow (churn) test | Electric fire pumps in high-rises beyond fire-service pumping capacity, with limited-service controllers, vertical turbine pumps, or suction from ground-level tanks | Weekly | Minimum 10 minutes | NFPA 25 (2023) §8.3.1.2 |
| No-flow (churn) test | All other electric fire pumps | Monthly | Minimum 10 minutes | NFPA 25 (2023) §8.3.1.2 |
| Annual flow test | All fire pumps | Annually | Minimum, rated, peak load | NFPA 25 (2023) §8.3.3 |
| Periodic test runs & maintenance | All fire pumps (India) | Per IS 15301 and pump manufacturer | Per IS 15301 and pump manufacturer | IS 15301:2003 |
| Continuous availability | High-rise buildings | 24/7 | Required residual pressure at the hydraulically remotest point | NBC 2016 Part 4 |
Required Log Columns
Each row of your weekly / monthly log captures these 15 columns. The PDF version formats this as a single landscape A4 sheet per test cycle.
Test date & time
Establishes the testing frequency was honoured.
Pump ID
Distinguishes electric/diesel/jockey pumps in mixed installations.
Test type
Weekly or monthly no-flow (churn) test, or annual flow test.
Run duration
Verifies the minimum test duration per NFPA 25 was achieved.
Suction pressure (start / running)
Detects supply-side issues, NPSH problems.
Discharge pressure (start / running)
Verifies pump performance vs the rated curve.
Flow rate (annual test only)
Compares measured flow to pump rating at min/rated/peak load.
Pump speed / RPM
Diagnostic for diesel pumps; abnormal RPM signals coupling issues.
Voltage & current (electric pumps)
Detects winding degradation, supply imbalance.
Battery voltage (diesel pumps)
Required by NFPA 25; battery health is a common failure point.
Coolant temperature (diesel pumps)
Verifies thermal management during the 30-minute no-flow run.
Jockey pump cycle count (since last test)
Abnormal cycling = early sign of system leakage.
Observations / abnormalities
Anything outside expected parameters.
Tested by (signature)
Auditable accountability.
Witnessed by (if applicable)
Required for some annual tests and insurance audits.
Common Audit Gotchas
- ▸Diesel no-flow run too short. NFPA 25 requires a 30-minute weekly no-flow (churn) test for diesel pumps. A 10-minute run satisfies the electric-pump rule, not the diesel one.
- ▸Electric pump on the wrong schedule. Monthly testing for electric pumps is the default in NFPA 25 (2023), not a blanket rule. A high-rise beyond fire-service pumping capacity, a vertical turbine pump or a ground-level tank suction keeps the pump on a weekly no-flow test.
- ▸No annual flow test on record. Many sites run weekly no-flow tests reliably but skip the annual flow test (which requires opening the test header / flow meter loop). Without it, the pump curve is unverified.
- ▸Jockey pump cycling not tracked. Frequent jockey starts are a leak indicator. If your log doesn't track the cycle count, you won't catch the leak until the next test.
- ▸Diesel battery voltage missing. Battery problems are a common reason diesel fire pumps fail to start on demand. NFPA 25's weekly diesel inspection covers the batteries and charger, so log the voltage every test cycle.
- ▸Pressure values without context. A discharge pressure of 7.0 kg/cm² is meaningless without knowing the rated pressure of the pump. Always log against the pump nameplate values.
Want to Stop Filling This in by Hand?
Titan Compliance combines an energy meter, pressure sensors and an inline flow meter on a DIN rail. It detects electric-pump runs from the motor's electrical signature, records run time, pressure and flow, flags missed tests and abnormal jockey cycling, and produces inspector-ready reports.
Visual checks in the pump room (leaks, packing, valve positions, diesel fuel and battery condition) still need a person, so keep a short manual checklist alongside it. Ask for a quote.
FAQ
Common questions about NFPA 25, IS 15301, jockey-pump diagnostics, and digital test logs.
Get the PDF version
A4 print-ready, branded, blank fillable form. Free — no signup.
